• Modular Online UPS 120~600KW Featured Image
  • Modular Online UPS 120~600KW

Modular Online UPS 120~600KW

Model: Modular UPS series 120-600kva (3-3Phase)

The modular UPS series 120-600KW (3ph in/3ph out) inbuilt  50KW~60KW power module and scalable from 120KW to 600KW, upto 1800KW  in parallel. High power density, easy for power expansion, installation and maintenance. Hot swappable power module and bypass & monitoring module with self-aging, smart sleep function. Applications in Government, Finance, IT, Data Centers, IT server rooms,  Manufacturing, Education, Transportation, Broadcasting, Medical, Energy, etc.

Features

Specification

Download

◆ The rack modular, hot-swapping, online double conversion

◆ High performance and efficiency, input PF>0.99, THDi<3%, efficiency >96%.

◆ Intelligent system self-diagnosis scheme, large capacity of history record storage space

◆ Redundancy fan design in power module, increasing the system reliability and tolerance.

◆ Top/bottom cable entry, flexible for different field installation.

◆ Easy for power expansion, installation and maintenance.

 

Our advantages

  • Our advantages

    To meet customized software and hardware

  • Our advantages

    To support SKD package for some countries imported request.

  • Our advantages

    7-15dasy delivery time for samples test

  • Our advantages

    Online quick reply on technical questions

REO UPS assemble line 1

Processing
materials

ODM & OEM production

We were established in 2015 , have two producing bases , 5 production line and monthly produce about 80,000 pieces.
Our ODM & OEM production is strictly based on the IS09001 and service customers in need.
REO is a one top power solution provider and warmly welcome to be our distributor and partner

Model M120/60 M180/60 M200/50 M240/60 M300/60 M480/60 M500/50 M600/60
Capacity 120KVA/120KW 180KVA/180KW 200KVA/200KW 240KVA/240KW 300KVA/300KW 480KVA/480KW 500KVA/500KW 600KVA/600KW
Phase Three phase input and Three phase output
Main input
Input 3P5W (3P+N+PE)
Rate Voltage 380/400/415VAC(L-L); 220/230/240VAC(L-N)
Rate Freq. 50/60Hz
Input PF >0.99
Current distortion THDi<3%(100% Linear load)
Voltage range 304~478VAC(L-L)full load;304~228VAC (L-L) power derate from 100% to 75%
Battery
Rate voltage ±240VDC
Charging capacity 20%*Output Capacity
Charging accuracy ±1%
Bypass
Rate voltage 380/400/415VAC(L-L)220/230/240VAC(L-N)
Voltage range Range: -40%- +25% , Settable, default -20%~+15%;
Overload 125%, long time operation
125%< load <130%, 10mins ;
130%<load <150%, 1min ;
Load>150%,300ms
110%, long time operation
110%< load<125%, 5 mins ;
125%<load<150%,1 min ;
Load >150%,1 second
Inverter
Rate voltage 380/400/415VAC(L-L);220/230/240VAC(L-N)
Rate Freq. 50/60Hz
Output PF 1
Voltage accuracy ±1.0%
Load response <5% (20% – 80% -20% step load)
Recovery time < 20ms (0% – 100% -0% step load)
Output THDu <1%(linear load),<5% (non-linear load according to IEC 62040-3)
Overload 110%,1 hour;125%,10 mins;150%,1 min;>150%,200ms
Frequency accuracy 0.001
Synchronize window Settable,±0.5Hz-±5Hz,default ±3Hz
Slew rate Settable,0.5Hz/S-3Hz/S,default 0.5Hz/S
Crest factor 3:1
Phase Accuracy 120°±0.5°
System
Efficiency Normal Mode≥96%;Battery Mode≥96%
Display LED + 7 inch touch LCD LED + 10 inch touch LCD
Certification- Safety IEC62040-1, IEC60950-1
Certification- EMS IEC62040-2; IEC61000-4-2(ESD); IEC61000-4-3(RS); IEC61000-4-4 (EFT) ; IEC61000-4-5 (Surge)
IP degree IP20
Configuration USB, RS232, RS485, Dry contact, Cold start, Air filter
Option SNMP card, AS400 card, Parallel kit, SPD, LBS
Environment 0-40℃(operation);  -25~70℃ (storage); 0-95% (Humidity, non-condensing)
Noise(dB)(1 meter) 72dB @ 100% load, 69dB @ 45% load
Dimension
Cabinet(W*D*H)mm 600*1000*1600 600*1000*2000 1200*1100*2000
Module(W*D*H)mm 442*659*174

Product specifications are subject to change without prior notice.